Testo
Testo 310 II-Flue Gas Analyzer
Model No :
Testo 310 II
Part Code :
0563-3104

Overview

Measurement accuracy, configurable measurement display, parallel measurement options, intuitive operation, sturdy housing, connection option to the testo Smart App: Our flue gas analyzer testo 310 II offers everything that heating fitters and technicians need for practical work on heating systems.

Major Applications
-Draught measurement in the flue gas duct
-Ambient CO measurement in the heated environment
-Measuring the flue gas parameters of the burner (CO, O2, and temperature, etc.)
-Measuring pressure on burners (nozzle pressure, gas flow pressure, etc.)

Features
-Easy and intuitive menu guidance
-Simultaneous, additional measurements via the testo Smart App
-Simultaneous, individual measurement and display of all relevant measurement parameters by (O2, CO, CO2, flue gas and ambient temperature, CO environment, draught and pressure)
-Digital documentation, data transfer and customer data management via testo Smart App

Technical Specifications
Technical Data
'-Temperature - TC Type K (NiCr-Ni)
-Measuring range:-20 to +100 °C
-Accuracy:±1 °C
-Resolution:0.1 °C
-Reaction time:< 50 s
-Temperature (ambient temperature)

Temperature - TC Type J (Fe-CuNi)
-Measuring range:0 to +400 °C
-Accuracy:±1 °C (0 to +100 °C)
±1.5 % of mv (> 100 °C)
-Resolution:0.1 °C
-Reaction time:< 50 s
-Temperature (flue gas):Flue gas O2
-Measuring range:0 to 21 Vol.%
-Accuracy:±0.2 Vol.%
-Resolution:0.1 Vol.%
-Reaction time t90:30 s
·Differential Pressure flue gas Draught - Piezoresistive
-Measuring range:-20 to +20 hPa
-Accuracy:±0.03 hPa (-3.00 to +3.00 hPa)
±1.5 % of mv (Remaining Range)
-Resolution:0.01 hPa
·Flue gas degree of effectivity, Eta (calculated)
-Measuring range:0 to 120 %
-Resolution:0.1 %
Flue gas loss (calculated)
-Measuring range:0 to 99.9 %
-Resolution:0.1 %
-Pressure measurement
-Measuring range:-40 to +40 hPa
-Accuracy:±0.5 hPa
-Resolution:0.1 hPa
-Flue gas CO (without H2-compensation)
-Measuring range:0 to 4000 ppm
-Accuracy:±20 ppm (0 to 400 ppm)
±5 % of mv (401 to 2000 ppm)
±10 % of mv (2001 to 4000 ppm)
-Resolution:1 ppm
-Reaction time t90:60 sAmbient CO
-Measuring range:0 to 4000 ppm
-Accuracy:±20 ppm (0 to 400 ppm)
±5 % of mv (401 to 2000 ppm)
±10 % of mv (2001 to 4000 ppm)
-Resolution:1 ppm
-Reaction time:60 s

General Specifications
General technical data
-Weight:Approx. 660 g
-Dimensions:201 x 83 x 44 mm
-Operating temperature:-5 to +45 °C
Display function:Graphic 7-line display
-Power supply:Battery: 1500 mAh, mains unit 5V/1A
-Storage temperature:-20 to +50 °C