Megger
Megger Egil Circuit Breaker Analyzer For One Break Per Phase
Model No :
Megger EGIL
Part Code :
- EGIL Basic unit :- BM-19090 Incl:- Time measurement cables :- GA-00160, GA-00170 - Cable set for sequencer GA-00082 Transport case :- GD-00190 - Co

Overview

The Megger's EGIL is an automatic timer and motion analyzer for medium- and high-voltage substation circuit breakers. It is intended for use on circuit breakers with one contact per phase. EGIL incorporates features commonly found on more complex test systems, but is designed to be smaller, simpler to use and less expensive than other similar test sets. It’s price makes it attractive to smaller utilities and it is an ideal supplementary product for maintenance departments at larger power companies and for testing contractors.

Features
- Suitable for testing timing and travel on all circuit breakers with single interrupter per phase
- Extremely easy-to-use and reliable
- Two separate timing channels for measurement of auxiliary contacts
- Analog measurement channels for travel transducers or general voltage/current measurements
- Static and dynamic resistance measurements along with the SDRM201 accessory

Major Applications
- The instrument is intended for use in medium-voltage substations and industrial environments
Technical Specifications
- Breaker operation Sequences: C, O, C-O, O-C, O-C-O
- Continuous current: 5 AMax current25 A during 300 ms, rest time 1 min
- Contact function: Two independent control functions
- Contact characteristics: Non bouncing, closing time max. 0.1 ms
- Make/Break capacity: 25 A, 250 V (AC or DC) per contact function
- Start breaker operation: By rotary switch
- Pulse length: Adjustable in steps of 10 ms
- Pulse delay: Adjustable in steps of 10 ms
- Working voltage: 250 V AC / DC
- Measurement time: 1 to 100 s
- Resolution: 0.1 to 10 ms
- Number of channels: 3 with common ground
- Time base inaccuracy: 0.05% of the reading ± resolution
- Status thresholds: Closed< 10 ? ±20%, Resistor10 ? ±20% to 3 k? ±20%, Open> 3 k? ±20%
- Open circuit voltage: 24 V ±20%
- Short circuit current: 100 mA ±20%

General Specifications
- Mains voltage: 115 / 230 V AC (switchable), 50 / 60 HzPower consumption100 VA (max)
- Dimensions Instrument: 360 x 210 x 190 -mm (14.2” x 8.3” x 7.5”)
- Temperature:
• Operating: 0°C to +50°C (32°F to +122°F)
• Storage & transport: -40°C to +70°C (-40°F to +158°F)
- Humidity: 5% – 95% RH, non-condensing
- Display: LCD
- Available languages: English, German, French, Spanish, Swedish
- CE-marking
• EMC: 2004/108/EC
• LVD: 2006/95/EC