Technical Specifications
- Insulation test: Voltages of 1,000/2,500/5,000/10,000/20,000 VMeasuring range of 650 MO
- HV Source: 40 kV DC proof testing and fault breakdown testing
- Breakdown detection: 0 to 40 kV
- Standard surge levels: 8 / 16 / 32 kV, 2,000 / 2,000 / 2,000 J
- Sheath testing and Sheath fault pinpointing Built-in prelocation: 3 kV, 5 kV, 10 kV, 20 kV0,5:1, 1:3, 1:4, 1:6
|
General Specifications
- Measuring range 20 m to 160 km at VOP = 80 m/µs
- Pulse width 20 ns to 10 µs
- Pulse amplitude 10 to 50 V
- Resolution 0.1 m at VOP = 80 m/µs
- Accuracy 0.1% Time base
- Accuracy 100 ppm
- Sampling rate true 400 MHz
- Dynamic range96 dB, with adjustable ProRange (Distance-dependent De-attenuation)
- Velocity of propagation10 ... 149.9 m/µs (or ft/µs or nvp)
- Output impedance 50 ?10 ? to 500 ?, adjustable
- ARM® trigger?U trigger technology with automatic adjustment
|