Megger
Megger PAT150 Handheld Portable Appliance Tester
Model No :
Megger PAT 150
Part Code :
1003-071

Overview

Megger PAT150 full functionality PAT tester adds to the offering Portable RCD (PRCDs) testing at 10 mA and 30 mA, separate tests for continuity, insulation, mains powered leakage testing and SELV measurements using the quick test (QT) button, and can be used for testing fixed appliances.

Features
- Simple tick or cross, pass or fail indication plus measurement
- Tough, rubber armoured with built-in front cover, hardened, scratch-proof display window
- Includes 250 V insulation and leakage testing for safe IT testing and surge protected devices
- Testing portable and fixed electrical equipment
- 10 mA and 30 mA portable RCD lead testing (PAT150)
- Adjustable PASS test limits (PAT150)
- Substitute and mains powered leakage testing (PAT150)
- Battery powered with rechargeable options

Major Applications
- Appliance Safety testing and reporting
Technical Specifications
- Continuity Test
- Test voltage Compliance voltage: +4 V dc -0% / +30% (open circuit)
- Test current : Bi-directional +200 mA
- Insulation Test : 250 V dc -0% +25% open circuit500 V dc -0% +25% open circuit= 500 V 0% dc across 0.5 MO load
-Substitute Leakage Test : Leakage current : Accuracy ± 5% ± 3 digits
- Test frequency : Nominal mains frequency 50 Hz
- Test voltage : < 50V ac, Resolution0.01 mA
- Display range 0.10 to 19.99 mA
- Differential Leakage Current :-Test voltage :- Nominal supply voltage : 230 V ac
- Test frequency : Nominal mains frequency 50 Hz
- Test accuracy ± 5% ± 3 digits ± 3 uA/A
- 10mA PRCD
- 30mA PRCD
- SELV Voltage
- Lead resistance Nulling

General Specifications
- Operating ambient : 20 °C
- Humidity : 45% rh ± 20 points
- Safety : Instrument designed to IEC 61010-1: 2012
- Test leads designed to IEC 61010-031: 200
- IP rating : IP 40