Honeywell
Honeywell - Vertex Multi-Point Toxic Gas Monitoring System
Model No :
Honeywell- Vertex
Part Code :
Kindly Contact for Final Configuration

Overview

The Honeywell Analytics Vertex™ System continuously monitors up to 72 remote locations for toxic gases. It helps in responding to gases that exceed programmed levels by:
• Triggering alarms and opening event windows to warn operators of high or low concentrations
• Triggering relays to external devices
• Displaying the location, gas type and gas concentration
• Storing the alarm information in a database
The Vertex System provides fast response to a wide range of gases. Each location may be up to 400 ft (122 m) from the Vertex System. The system uses one or more of Honeywell Analytics’ Chemcassette® analyzers, with or without pyrolyzer, to provide a monitoring system tailored to meet the requirements of the facility

Features
- Touch screen for easy data access
- Low cost of ownership with Chemcassettes
- One systems monitors up to 9 gas families/more than 40 gases

Major Applications
- Laboratory/medical

Technical Specifications
- Relay output contacts: Via PLC, normally open
(form A). Available in 88 and 176 contacts, both are
user configurable
- Relay Contact Ratings:
• 0.1 to 2.0 Amps
• 5-24 VDC or
• 5-120 VAC
- Network interface options currently available on
Vertex are standard
- OLE for Process Control (OPC) Interface: The Vertex monitor’s primary method of alarm and fault annunciation relies on the Allen Bradley SLC500 PLC system installed in the base enclosure using optional fieldbusses or contact closure
- ControlNet a real-time, control-layer network: Providing for high-speed transport of both timecritical I/O data and messaging data, including upload/download of programming and configuration data and peer-to-peer messaging, on a single physical media lin

General Specifications
- Height: 76 in. (193 cm)
- Width: 24 in. (61 cm)
- Depth: 34-1/2 in. (88 cm)
- Installation Category: (overvoltage category): II (UL 61010B-1)
- Temperature: 59°F to 95°F (15°C to 35°C)
- Humidity: 20-80% RH
- Operating Altitude: –1000 ft. (–305 m) to 6000
ft. (1829 m) above sea level
- Operating Voltage: 230 VAC ± 10%