Technical Specifications
- Electrical Power: 24 Volts DC regulated, 1.0 amp - Output: Linear 4/20 mA output into a load resistor of 500 ohms maximum - Cable Length to Sensor: 1,000 feet maximum - Gases Monitored R-404a, R-22, R-507a, R-513a, R-514a, R-134a, R-407a, R-410a, R-422d, R-448a, R-449a, HFO-1234yf, HFO-1234ze, HFO-1233zd, NH3, CO2 - Gas Sampling Diffusion method with no moving parts, real time continuous monitoring of all points - Accuracy +/- 3% full scale - Repeatability +/- 1% full scale - Repeatability +/- 1% full scale - Type: CFC/HCFC/HFC selective infrared gas sensor/ transmitter AirScanTMiR - Sensor Specifications: • Response Time T90 = 10 seconds • With full-scale calibration gas @ .75 litres/min. flow rate • Ranges R Gases: 0-500 ppm, 0-1,000 ppm, 0-3,000 ppm
|
General Specifications
- Humidity: 0-100% RH (condensing) - Operating Temperature: • Standard: -30°C to +60°C / -20°F to +140°F • ATMOS: 40°C to +60°C / -40°F to +140°F • Superheat: -50°C to +60°C / -60F to +140°F - Storage Temperature: -28°C to +60°C / -20°F to +140°F • Enclosure: 16 gauge painted steel or stainless steel.
|