Technical Specifications
- Electrical Power: 24 Volts DC regulated, 1.0 amp
- Output: Linear 4/20 mA output into a load resistor of
500 ohms maximum
- Cable Length to Sensor: 1,000 feet maximum
- Gases Monitored R-404a, R-22, R-507a, R-513a, R-514a, R-134a, R-407a, R-410a, R-422d, R-448a, R-449a, HFO-1234yf, HFO-1234ze, HFO-1233zd, NH3, CO2
- Gas Sampling Diffusion method with no moving parts, real time continuous monitoring of all points
- Accuracy +/- 3% full scale
- Repeatability +/- 1% full scale
- Repeatability +/- 1% full scale
- Type: CFC/HCFC/HFC selective infrared gas sensor/
transmitter AirScanTMiR
- Sensor Specifications:
• Response Time T90 = 10 seconds
• With full-scale calibration gas @ .75 litres/min. flow rate
• Ranges R Gases: 0-500 ppm, 0-1,000 ppm, 0-3,000 ppm
|
General Specifications
- Humidity: 0-100% RH (condensing)
- Operating Temperature:
• Standard: -30°C to +60°C / -20°F to +140°F
• ATMOS: 40°C to +60°C / -40°F to +140°F
• Superheat: -50°C to +60°C / -60F to +140°F
- Storage Temperature: -28°C to +60°C / -20°F to +140°F
• Enclosure: 16 gauge painted steel or stainless steel.
|