Honeywell
Honeywell E3 Point gas monitor
Model No :
Honeywell E3 Point gas monitor
Part Code :
Kindly Contact for Final Configuration

Overview

The Honeywell E3 Point gas monitor is a toxic/combustible gas monitor that makes a commercial operation run more intelligently to protect people, property and the bottom line.
E3Point is capable of detecting the widest range of toxic and combustible gases found in commercial building spaces and outbuildings, including CO, NO2, O2, H2, H2S, CH4 and C3H8. It can be used as a standalone unit with single or dual-gas detection (i.e. using a remote sensor) or deployed as a networkable device (interoperable with BACnet, Modbus or other Building Automation System).
E3Point also functions with existing controller-based gas monitoring systems and wired-wireless gas monitoring system components.

Features
- Standalone, standalone with remote (dual gas mode) or network versions available
- Saves energy through Demand Control Ventilation
- Advanced sensing technology detects CO, NO2, O2, H2, H2S, CH4, C3H4

Major Applications
- Parking Structure
- Loading Dock
- Transport Terminal
- Golf Cart Maintenance/Battery Charging Area
- Maintenance Garage
- Hospital/Ambulance Bay
- Fire/Police Station
- Boiler Room
- Battery Charging Rooms H2 & Hydrogen Tanks
- Commercial Kitchen
- Indoor Stadium/Arena

Technical Specifications
- Power Requirement 24 Vac nominal (17-27Vac), 50/60 Hz, 0.35 A; 24Vdc nominal (20-38Vdc); with remote sensor: 7 W max.
- Optional Main AC Input 120Vac nominal, ± 10% (with on-board transformer)
- Output: Circuit board mounted sensor provides a linear 4-20 mA output. Monitoring
equipment may have a maximum impedance of 500 ohms
- Relay Output 2 DPDT relays, 5A @ 250Vac; 5A @ 30Vdc
- Communications 4-20mA
- Response Time: T90 < 50 seconds With ECLAB T90 < 240 seconds
- Display: 8 character, 2 line backlit LCD
- Audible Alarm: >85 dBA at 3 m (10 ft)
- Accuracy: ± 3% of full scale @ 25ºC

General Specifications
- Uses Wall or duct-mounted gas detector for monitoring carbon monoxide (CO), nitrogen dioxide (NO2), oxygen (O2),methane (CH4), hydrogen (H2), hydrogen sulphide (H2S), and propane (C3H8), installed as a standalone device
- Operating Environment Commercial, Indoor, Extreme temperature environments
- Operating temperature: H2S, NO2, O2, CH4, H2, C3H8: -40 to 50ºC (-40 to 122ºF)CO: -20 to 50ºC (-4 to 122ºF)
- Sensor Type Electrochemical cell (CO, NO2, H2S, O2); catalytic (CH4, H2, C3H8)
- Enclosure: Polycarbonate
- Certification: CSA C22.2 No. 61010-1, UL 61010-1; FCC part 15; ICES-003 issue 4; ISO 9001-2008