Overview

Honeywell Touchpoint™ Plus is an easily configurable, wall mounted control system that supports up to sixteen channels of gas detection. Its intuitive user interface and modular approach enables you to take control of your safety system and configure it to meet your needs for a wide range of applications.
With its unique user interface, operators are able to take control of their gas detection system, safe in the knowledge that their site and staff are protected and productivity is maintained.
Designed to work across multiple industries, Touchpoint™ Plus' modular architecture enables you to customize your system to meet your specific application requirements.

Features
- Quick and easy setup and use
- Intuitive touchscreen user interface
- Traffic light style status at a glance
- Ergonomic industrial design
- Suited to a wide range of industries

Major Applications
- Drilling rigs
- Petrochemical plants
- Tank farms
- Shipyards and maritime
- Steel mills
- Industrial safety

Technical Specifications
- Power Supply:
• Power AC 110/220VAC, 50-60Hz Manual switching
• Power DC 18 to 32 VDC (+/-10%) Typical 24VDC
- Power Consumption Max 105W (including detector and external devices), max 210W with expansion unit
- Available I/O Modules: 4-20mA Input 2 or 3 wire, 2/4/8 channel modules,10/12/16 with expansion unit
- mV Input: Catalytic type flammable gas detectors(Honeywell models). 2/4/8 channel modules, 10/12/16 with expansion unit
- Dual Input: 2 channel mA + 2 channel mV module or 4 channel mA + 4 channel mV module
- Relay Output: 12 or 24 relay outputs, NO/C/NC changeover, 1.7A@30VDC/250VAC,user configurable - energised/de-energised,latching/non latching, time delay
- 4-20mA Output:4 or 8 isolated repeated mA outputs,
0-22mA, 0-100%FSD = 4-20mA
- Common Inputs: Remote reset, remote inhibit
- Common Outputs: Four powered A/V outputs for alarms and fault, three common alarm outputs
- Data logging :Configuration, logged events and data
- Communication :MODBUS TCP, WEB monitoring and
MODBUS RTU

General Specifications
- Capacity Up to 8 channels with base unit, up to 16
channels with expansion unit.
- Display: 7’’colour LCD touchscreen. Graphic User Interface
- Audible Alarm = 70dB @ 1m
- Button: Common for reset/mute operation
- Language: English, French, German, Italian, Dutch,
Spanish, Portuguese, Russian, Chinese
- Operating: -10 °C to +55 °C (14 °F to +131 °F) continuous, up to 95% RH
- Approval: Electromagnetic Compatibility and Electrical Safety
• EMC/RFI (EN 50270:2015)
• LVD (EN 61010-1:2010)
• CSA-C22.2 No. 61010-1-04
• UL 61010-1 (3rd Edition) and 508
- Safety Integrity :IEC 61508:2010 Ed.2 SIL2, EN
50271:2010
- Hazardous Location: Class I, Division 2, Group A, B, C and D or non-hazardous only