Rae guard 3 provides users with safer, more stable, more reliable and more effective field transmitter, and can be applied in indoor and outdoor hazardous environments, to monitor the dangerous degree of hazardous gases in real time, so as to rapidly and effectively protect.

Features
- Wider compensation for temperature and environmental factors keeps the instrument reliable and stable
- Redundant design to ensure no false alarm
- Clear indications of status can perceive the degree of environmental hazards even at long distances
- Optional integrated visible and sound alarm, light and sound constantly remind, alarm signal will not be ignored
- Optional built-in surge protection device to make sure outdoor installation of worryfree

Major Applications
'- Chemical industry
- Oil & Gas Storage and Transportation
- Food/beverage
- Refineries
- Power plants
- Steel plants
- Laboratory
- Waste water facilities
- Utilities
- Pharmaceutical plant
- Chemical Storage
- Automotive industry

Technical Specifications
- Input voltage: 16~32VDC (rated: 24VDC)
- Maximum power consumption: Electrochemistry: 5.5W; Catalytic combustion/NDIR, 7.5W
- Current output: Standard fully configurable 4-20mA (source type), optional carrier independent HART 7.2 output (optional)
- Relays: 3 x 2A@30VDC. Selectable normally open or normally closed and energised/de-energised(programmable) and latch/non-latch Alarm relays default energised/non-latch. Fault relay default energised/non-latch
- Communication: RS485, Modbus RTU, Optional Bluetooth

General Specifications
- 3/4” NPT M, 1/2” NPTM/F, G3/4” M/F, G1/2” F and M20 F varied glands selectable.
- Integral mounting plate or optional rewarded backboard mount kit for easy wall or pipe mounted
- EMC: EN50270:2015, IEC61000-4-5
- Performance: IEC 60079-29-1, EN 50104
- IEC 61508 (SIL Assessment, SIL2)
- IP Rating Toxic and Oxygen: IP66/67 LEL/NDIR: IP66
- Operating Temperature: -40°C~+70°C
- Operating Humidity: LEL/NDIR: 0~95%RH (Non-condensing)
Toxic and Oxygen: 15%~95%RH (Non-condensing)
- Operating Pressure: 90~110kPa
- Storage Conditions: -20°C~+50°C, 45-75%RH(Non-condensing), in clean air